TeSys GV motor circuit breaker, 3 poles (3P), 65A/690V, for 3-phase motor applications 30kW@400V. It provides a thermal-magnetic protection with a thermal setting range 48-65A, magnetic tripping at 15xIn, high breaking capacity Icu 50kA@400V. Connection by Everlink BTR screw terminals. Start-stop control by rotary knob guaranteed for 50 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
Specifications
Main
Range |
TeSys Deca |
Product name |
TeSys GV3
TeSys Deca |
product or component type |
Motor circuit breaker |
Device short name |
GV3P |
Device application |
Motor protection |
Trip unit technology |
Thermal-magnetic |
Complementary
poles description |
3P |
Network type |
AC |
Utilisation category |
AC-3 conforming to IEC 60947-4-1 |
Network frequency |
50/60 Hz conforming to IEC 60947-4-1 |
Fixing mode |
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 3 x M4 screws) |
Motor power kW |
30 kW at 400/415 V AC 50/60 Hz
45 kW at 500 V AC 50/60 Hz
55 kW at 690 V AC 50/60 Hz |
Breaking capacity |
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
12 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ics] rated service short-circuit breaking capacity |
100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
Control type |
Rotary handle |
[In] rated current |
65 A |
Thermal protection adjustment range |
48…65 A conforming to IEC 60947-4-1 |
Magnetic tripping current |
910 A |
[Ith] conventional free air thermal current |
65 A conforming to IEC 60947-4-1 |
[Ue] rated operational voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2 |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2 |
Phase failure sensitivity |
Yes conforming to IEC 60947-4-1 |
Suitability for isolation |
Yes conforming to IEC 60947-1 |
Power dissipation per pole |
8 W |
Mechanical durability |
50000 cycles |
Electrical durability |
50000 cycles for AC-3 at 415 V In |
Rated duty |
Continuous conforming to IEC 60947-4-1 |
Tightening torque |
5 N.m – on screw clamp terminal |
Width |
55 mm |
Height |
132 mm |
Depth |
136 mm |
net weight |
0.96 kg |
Colour |
Dark grey |
Environment
Standards |
EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1 |
Product certifications |
CCC
UL
CSA
EAC
ATEX
LROS (Lloyds register of shipping)
BV
ABS
DNV-GL
UKCA |
IK degree of protection |
IK09 enclosure |
IP degree of protection |
IP20 conforming to IEC 60529 |
Climatic withstand |
Conforming to IACS E10 |
ambient air temperature for storage |
-40…80 °C |
Fire resistance |
960 °C conforming to IEC 60695-2-11 |
Ambient air temperature for operation |
-20…60 °C |
Mechanical robustness |
Shocks: 15 Gn for 11 ms contactor open
Shocks: 30 Gn for 11 ms contactor closed
Vibrations: 4 Gn, 5…300 Hz |
Operating altitude |
3000 m |
Reviews